E-STOP Pushbuttons, Safety Gates Safety Relay
CZSR8001-3A1B  E-STOP Pushbuttons, Safety Gates Safety Relay
CZSR8001-3A1B is suitable for emergency stop button, safety control switch input, with 3 NO (normally open) safe output contacts and 1 way NC (normally closed) auxiliary output contact of the safety relay. It can choose single and double channel operation, manual or automatic reset, and has the function of monitoring the short circuit between channels.
CZSR8001-3A1B
产品详情
产品参数
下载
click to consult
加入对比
加入询价单

E-STOP Pushbuttons, Safety Gates Safety Relay

E-STOP Pushbuttons, Safety Gates Safety Relay


Product Name  CZSR8001-3A1B E-STOP Pushbuttons, Safety Gates Safety Relay
Number of channels  4 inputs/4 outputs
Supples voltage(Ue)  20.4V~26.2V DC
Input signal  Switch: E-STOP Pushbuttons, Safety Gates
Output signal  Relay: 3NO+1NC
Ambient temperature  -20℃~+60℃
Certification
 TUV SIL3;CE;PLe; Cat.4

E-STOP Pushbuttons, Safety Gates Safety Relay

E-STOP Pushbuttons, Safety Gates Safety Relay

E-STOP Pushbuttons, Safety Gates Safety Relay


E-STOP Pushbuttons, Safety Gates Safety Relay


Product characteristics
Product application
General
Input data
Output data
Power supply
Dimensions
Housing
Product approvals
Standard/Specification
Safety-related parameters(SIL)
EMC data
Safety-related parameters(PL)
Operating conditions
Connection data
Installation
产品参数
Product characteristics
Characteristics 3NO+1NC;single or dual channel operation
Product application
Application E-STOP Pushbuttons, Safety Gates
General
Number of channels 4inputs/4outputs
Response time 300ms
Electromagnetic compatibility According to IEC 61326-1(GB/T 18268), IEC 61326-3-1
Field apparatus E-STOP Pushbuttons, Safety Gates
Input data
Input signal Switch
Input current ≤50mA
Normal working current ≤50mA
Input apparatus E-STOP Pushbuttons, Safety Gates
Output data
Output signal Relay
Number of contacts 4
Contact material AgSnO2+0.2um AU
Contact type 3NO+1NC
Contact fuse protection 10A gL/gG NEOZED(NO),6A gL/gG NEOZED(NC)
Switching capacity AC-15,5A/230V;DC-13,5A/24V
Switch-on delay ≤300ms
Supply interruption before de-energisation 20ms
Delay on de-energisation ≤30ms
Recovery time ≤100ms
Power supply
Supply voltage(Ue) 20.4V~26.2V DC
Power protection Reverse protection of power supply
Current consumption ≤90mA (at 24Vdc supply)
Power supply mode Independent power supply
Power connecting mode Terminal
Dimensions
Depth 114.5mm
Height 99.0mm
Width 22.5mm
Housing
Material PA
Degree of protection IP20
Flammability rating UL94/V0
Colour gray
Product approvals
Approvals SIL(TUV);CE
Standard/Specification
Functional safety SIL3 Comply with standard: IEC 61508
CE MD Directive;LVD Directive
Safety-related parameters(SIL)
Type of equipment Type A
Safety integrity level(SIL) 3
Mode of operation (Low demand) IEC 61508-Low demand
Safe failure fraction(Low demand) (SFF) ≥99%
Proof test interval(Low demand) (PTI) 20 years
λS(Low demand) 8.59E-07
λDU(Low demand) 6.06E-09
λDD(Low demand) 6E-07
Average probability of dangerous failure on demand(Low demand) (PFDAVG) 2.69E-05
Diagnostic coverage(Low demand) (DC) ≥99%
Mode of operation (High demand) IEC 61508-High demand
Safe failure fraction(High demand) (SFF) ≥99%
Proof test interval(High demand) (PTI) 20 years
λS(High demand) 8.59E-07
λDU(High demand) 6.06E-09
λDD(High demand) 6E-07
Average frequency of a dangerous failure per hour(High demand) (PFH) 3.09E-10
Diagnostic coverage(High demand) (DC) ≥99%
EMC data
Electrical fast transient/burst immunity According to:IEC 61326-3-1
Surge immunity According to:IEC 61326-3-1
Radiated,radio-frequency,electromagnetic field immunity According to:IEC 61326-3-1
Electrostatic discharge immunity According to:IEC 61326-3-1
Immunity to conducted disturbances, induced by radio-frequency fields According to:IEC 61326-3-1
Immunity to conducted, common mode disturbances in the frequency range 0 Hz to 150 kHz According to:IEC 61326-3-1
Safety-related parameters(PL)
Performance level (PL) PLe
Category (Cat) Cat.4
Stop category 0
Mission time (TM) 20 years
Diagnostic covery (Dcavg) ≥99%
Mean time to repair (MTTR) 0
Mean time to dangerous failure (MTTFd) 188 years
Number of cycles until 10% of the components fail dangerously (B10d) 300000(5A)
Operating conditions
Ambient temperature -20℃~+60℃
Storage temperature -40℃~+80℃
Relative humidity 10%~90%
Environmental requirements The air should not contain any medium corrupting the coat of chrome,nickel and silver.Moreover,violent quiver and impact or any cause of electromagnetic induction (such as big current or spark,etc.)must be avoided when using
Connection data
Conductor cross section solid range 0.5~2.5mm²
Conductor cross section flexible range 0.5~2.5mm²
Conductor cross section AWG min. 12
Conductor cross section AWG max. 24
Stripping length 8mm
Screw thread M3
Connection method Screw connection
Tightening torque min. 0.5 Nm
Tightening torque max. 0.6 Nm
Installation